OxyBalance Oxygen Display and Averaging System
Large combustion processes continually require improved gas analysis in order to maintain the best heat rate performance. The OxyBalance system is a display and averaging system that assists plant operations in setting overall fuel/air ratios as well as providing a tool for balancing individual burners or sets of burners.
|
- Graphically displays and trends from 1 - 8 oxygen measurements
- Probe inputs may be from Rosemount Analytical, Westinghouse, or any competitive oxygen probe with a 4-20 mA signal output
- Auto Sense- automatically detects probes when they are wired into the system
- Individual probe readings remain autonomous and are unaffected by any potential failure of the OxyBalance unit
- No single point of failure- individual probe 4-20 mA signals going to the DCS are unaffected by a power supply or other failure of the OxyBalance
- Temperature Specification: -5ºC to 35ºC
- Ambient temperature effect on electronics: Less than .01% of reading per 10ºC
- Vibration: IEC 68-2-6 and ISA S37.3
- Shock: IEC 68-2-31 and ISA S37.3
- Enclosure: NEMA 4X
- Area Classification: General Purpose
- Power Requirements: 110V/240V, 50/60 Hz.
- Used for control purposes
- Diagnostic tool for:
- Balancing burners
- Detecting burner fouling
- Detecting roping in coal pipes
- Mill to mill variations
|
|
|