0-1% to 0-40% O
2 Fully field-selectable via HART or LOI
Combustibles: 0-1000 ppm to 0-5% Fully field-selectable via HART or LOI
Accuracy: Oxygen : ± .75% of reading or .05% O
2, whichever is greater
Combustibles: ± 2% F.S.
System Response to Test Gas: O2: 10 sec T90
Combustibles: 25 sec T90
Temperature Limits:
32° to 2600°F (0° to 1427°C)
Sensors Housing: -40° to 212°F (-40° to 100°C)
Electronics Housing: -40° to 149°F (-40° to 65°C)
Probe Lengths, Nominal and Approximate Shipping Weights:
54 pounds (24.5 kg)
3 foot (0.91 m) package: 55 pounds (24.5 kg)
6 foot (1.83 m) package: 57 pounds (26 kg)
9 foot (2.74 m) package: 59 pounds (26.8 kg)
Materials:
316L stainless steel – 1300°F (704°C) Inconel 600 – 1832°F (1000°C) Ceramic – 2600°F (1427°C)
Enclosures: Low-copper aluminum
Calibration: Semi-automatic or automatic
Calibration Gas mixtures recommended: 0.4% O
2, balance N
2 8% O
2, balance N
2 1000 ppm CO, balance air
Calibration Gas Flow: 7 scfh (0.5 l/m)
Reference Air: 2 scfh (1 l/m), clean, dry, instrument- quality air (20.95% O
2), regulated to 35 psi (238 kPa)
Eductor Air: 5 scfh (2.5 l/m), clean, dry, instrument-quality air (20.95% O
2), regulated to 35 psi (238 kPa)
Dilution Air: .1 scfh (0.5 l/m), clean, dry, instrument-quality air (20.95% O
2), regulated to 35 psi (238 kPa)
Blowback Air: Clean, dry, instrument quality air
(Optional) (20.95% O
2 ) regulated to 55 psi (374 kPa)
Sensors Housing: NEMA 4, IP66 Two 3/4" – 14 NPT conduit ports
Electronics Housing: NEMA 4, IP66 Two 3/4" – 14 NPT conduit ports
Electrical Noise: EN 61326-1, Class A
Optional Hazardous
- Area Certifications: CSA/FM Class 1, Zone 1 Ex D IIB + H2 T3/T6 AEx D IIB + H2 T3/T6 ATEX II 2 G EEx D IIB + H2 T3/T6
- The OCX 8800 complies with the European Union PED 97/23/EC Directive by virtue of SEP. (Split architecture only)
- Line Voltage: 100-240 VAC ± 10% 48-62 Hz. No switches or jumpers required 3/4" – 14 NPT conduit port
- Isolated Output: O2, 4-20 mAdc, 950 ohm maximum with HART capability COMB, 4-20mAdc, 950 ohm maximum
- Alarm output relay: dry contact, 30 mA and 30 VDC capacity
- Logic Signals: SPA HART® ALARM module (optional) Low O2 alarm High Comb alarm Calibration status Unit failure
- Power Consumption Limits: Power Consumption of Heaters: 750 W nominal maximum
- Power Consumption of Electronics: 50 W nominal maximum