- Differential Pressure calculated using two 3051S pressure sensors
- 2-Wire, 4-20 mA HART architecture
- Available process variables include DP, PHI and PLO Pressures, and Scaled Variable for tank level or volume
- SFF:
- Two Coplanar sensors: 92.9%
- One Coplanar and one In-Line sensor: 93.7%
- Two In-Line sensors: 94.6%
- PFDAverage (proof test interval equals 1 year):
- Two Coplanar sensors: 1.25E-03
- One Coplanar and one In-Line sensor: 1.10E-03
- Two In-Line sensors: 9.79E-04
- Available with flanged, NPT, Instrument manifolds, and direct mount seal process connections
|