Mobrey 003 Ultrasonic Integral Gap Sensor Level Switch
Manufactured in Polyphenylene Sulphide (PPS) for corrosion resistance in most liquids, the 003 range of ultrasonic liquid level switches can be mounted in any position in a tank using either a 25mm/1" or 19mm/¾" thread available in BSPP, BSPT and NPT thread forms. A thread is provided on each side of a hexagonal boss to allow either external or internal / pole mounting of the sensor. Comprising a one piece moulded body with an integral pcb, the 003 switch is factory sealed and supplied with a 3m/10ft flying lead for customer connection.
The Mobrey 003 ultrasonic liquid level switch is designed for high or low level alarm duties to give a voltage free contact or solid state transistor output for alarm signalling or as part of a pump control system.
The 003 ultrasonic sensor may be mounted at any angle in the vessel.
|
Features
- Relay or solid-state output
- Corrosion resistant PPS construction
- 25mm/1" or 19mm/¾" threaded mounting
- Small in-tank dimensions
- 24V ac or dc powered
- Lightweight
Benefits
- Self contained liquid level alarm
- No moving parts
- European Directive compliance
|
|
| |
|
|
| Operating Pressure |
290 psi (20 bar) |
290 psi (20 bar) |
| Operating Temperature |
–4 to +158 °F (–20 to +70 °C) |
–40 to +221 °F (–40 to +105 °C) |
| Ambient Temperature |
Same as operating temperature |
Same as operating temperature |
| Minimum Specific Gravity (SG) |
0.50 |
0.50 |
| Maximum Viscosity |
5000 cSt at 68 °F (20 °C) |
5000 cSt at 68 °F (20 °C) |
| Switching Response |
50 ms dry-to-wet, 0.5 s wet-to-dry |
50 ms dry-to-wet, 0.5 s wet-to-dry |
| Hysteresis |
< 0.12 in. (4 mm) |
< 0.12 in. (4 mm) |
| Repeatability |
±0.08 in. (2 mm) |
±0.08 in. (2 mm) |
| Overall Length |
4.33 in. (110 mm) |
4.33 in. (110 mm) |
| Length Into Tank |
3.11 in. (79 mm) when external mount |
3.11 in. (79 mm) when external mount |
| Body Diameter |
0.87 in. (22 mm) |
0.87 in. (22 mm) |
| Switching Function |
SPCO relay (energised when wet) |
2 x FET open drain (short circuit protected) |
| Maximum Switched Current |
1 A at 30 V residual 0.25 A at 30 V inductive |
100 mA maximum |
| Maximum Switched Voltage |
30 V |
30 V |
| Power Supply |
18 to 30 Vdc or Vac |
18 to 30 Vdc or Vac |
| Dry Current Drawn |
10 mA nominal |
8 mA nominal (4 mA minimum) |
| Wet Current Drawn |
25 mA maximum |
16 mA nominal (20 mA maximum) |
| Cable Length |
10 ft (3 m) 5-core 7/0.2mm (0.008 in.) |
10 ft (3 m) 4-core 7/0.2mm (0.008 in.) |
| Cable Sheathing |
PVC |
PVC |
| IP Rating of Sensor |
NEMA 6P (10 ft) / IP66/IP68 (3 m) |
NEMA 6P (10 ft) / IP66/IP68 (3 m) |
| Notes: Not suitable for use in intrinsically safe circuits. Not suitable for the direct starting of large motors | Applications
- Low level alarms in header tanks
- Pump control duty in feeder tanks
- High and low alarms in storage tanks
- Level and pump control in storage tanks
- Small or thin wall tanks
- Bund level detection
- Steering gear oil
|
|
|